A detection retrofit that runs over budget usually does so in the cable and not in the detectors. Heads and panels are quantified early. The routing, the cable type and the separation get settled on board, late, and quite often twice.
The FSS Code is brief on this subject and quite specific, and reading it in full before a cable schedule is priced removes most of the rework that follows.
What Cable Type Does The FSS Code Require?
Cables used in the electrical circuits of a fixed fire detection and fire alarm system shall be flame retardant according to standard IEC 60332-1. That is the baseline for every ship type, and it applies to the circuits themselves and not to the equipment they connect.
The distinction between flame retardant and fire resisting is the one to hold onto. A flame retardant cable resists carrying a fire along its own length. A fire resisting cable keeps a circuit alive while a fire burns around it. The Code asks for the first everywhere and the second only in the passenger ship cases set out below.
Passenger ships carry an additional requirement. Cables routed through main vertical zones other than the zone they serve, and cables to control panels in an unattended fire control station, shall be fire resisting according to standard IEC 60331, unless they are duplicated and well separated. The Code sets no separation distance, so what counts as well separated is settled with the Administration or the recognised organisation, and it is better agreed at the drawing stage than at commissioning. Resolution MSC.311(88) carries the current chapter text, and the IMO summary of Chapter II-2 shows where the detection and alarm requirement itself sits, at Regulation 7, which is what pulls the FSS Code chapter into force for a given ship.
Where a loop is being extended or re-terminated, the fire detection ancillaries that carry, terminate and protect the cable are held in Singapore alongside the cable itself, which keeps the replenishment leg short for vessels running marine fire detection systems through the Strait of Malacca.
Where Must Detection Cable Not Be Routed?
Cables forming part of the system shall be arranged so as to avoid galleys, machinery spaces of category A, and other enclosed spaces of high fire risk, except where it is necessary to provide fire detection or fire alarms in those spaces or to connect to the appropriate power supply.
The exception is doing a great deal of work in that sentence. A loop obviously has to enter a machinery space in order to serve it, so the requirement bites on cable that merely passes through on its way somewhere else. Transit routing is where retrofits most often fall short, because the shortest run between two compartments frequently crosses a third that the Code would rather it avoided.
What Does The Single-Point Fire Damage Rule Mean In Practice?
A section with individually identifiable capability shall be arranged so that it cannot be damaged at more than one point by a fire. The design consequence is that the outbound and return legs of an identifiable section should not share a route where one fire would take both.
Backup power for marine fire alarm panels and the cable that reaches them form part of the same survivability question, and a loop that is electrically protected but physically routed through a single trunking is only half solved. The Code requires not less than two sources of power supply for the electrical equipment operating the system, one of them an emergency source, with an automatic change-over switch in or adjacent to the control panel.
Which Standards Should Appear On The Cable Schedule?
Four references cover most of a detection installation. Quoting them on the schedule removes ambiguity at the procurement stage and shortens the approval conversation.
- IEC 60332-1, flame retardance, for cables used in the electrical circuits of the detection and alarm system.
- IEC 60331, fire resistance, for the passenger ship routing cases described above.
- IEC 60092-504, applied by the Code to testing of the control panel, heat detectors and linear heat detectors.
- EN 54-2:1997 and EN 54-4:1997, applied by the Code to testing of the control panel.
The last two are testing references for equipment and not cable specifications, and confusing the two categories is a common source of a rejected submission. Note also that linear heat detection sensor cable is treated as a detector under the 2026 amendments, with its own testing reference, and not as a circuit cable.
How Does This Change A Retrofit Scope?
Cable is the item that turns a detector count into a dry dock package. Once the routing constraints above are applied, run lengths rise, the number of gland plates and bulkhead transits rises with them, and the labour follows both.
Pricing the cable schedule against the routing constraints before the docking specification is issued produces a far more honest number, and it exposes early the cases where a second riser is cheaper than a compliant detour. Lead times on marine-rated cable vary with vessel type, cable construction and availability, so any figure quoted well in advance should be treated as indicative.
Recording the as-fitted routing at the end of the job is the step that pays for itself next time, because the following retrofit then starts from a drawing instead of from a survey. Fleets that skip it end up paying twice for the same information.
Specify The Cable With The Rest Of The Package
A detection package priced without its cable schedule is priced twice. Atlas Technologies Corporation is a Singapore-based supplier and an authorised distributor for Tyco, Federal Signal and Solo, supplying detection equipment, ancillaries and marine ship spares to fleet owners, technical superintendents and procurement teams across Singapore, Malaysia, Indonesia, Greece and Turkey. Speak to our team while the routing is still on paper, and we will help you line the schedule up with what the Code asks for.