Tyco MPM800 Multi Purpose Interface Module 557.202.012
The Tyco MPM800 provides various expansion capabilities via the remote bus (RBUS). Tyco MPM800 provided as a standalone module but also incorporated into the circuitry of the OCM800 operator control module to drive the LCD display, LEDs, keyswitch and keys
on the OCM800 and the operator display module. The OCM800 and MPM800 have an XBUS which can be used to drive up to 80 I/O.
Tyco MPM800 also has a printer interface for connecting to a serial or parallel printer. An additional printer driver kit required to allow the MPM800 to drive a printer – used a serial isolation module to eliminate earth fault indications caused by some mains connected printers.
Up to 15 x MPM modules connected to each panel of which 8 can be in the form of OCM800 (including the main OCM800 user interface). One OCM800 can also be in the form of an emulated user interface on a remote PC connected via the network or dial up modem.
The following I/O and LED annunciator modules can be slaved from an MPM800:
- Up to 5 x IOB800 (8 in/8 out expansion board)
- Up to 5 x XIOM800 (16 way universal I/O board)
- One Mimic Panel (80 way LED mimic driver PCB)
- One 80 way ANN880 LED mimic **
- One 40 way ANN840 LED mimic using red & yellow LEDs **
- One 20 way COM820 LED status/command modules **
The MPM800 mounted by plugging directly onto the back of those items marked **
Key features include:
- Drives up to 80 I/O points
- Direct interface to zonal displays and other modules
- Interfaces to FIM Board
- Product Code: MPM800 (557.202.012)
How to order (Specify Model): Select MPM800 (557.202.012)
Part Number | Description |
557.202.012 | Tyco MPM800 Multi Purpose Interface Module |
557.202.117 | Serial Printer Cable for MPM800 or FIM800 |
557.180.052 | Serial Printer Driver Kit (Only required for earlier MPM800 modules) |
557.180.053 | Isolated RS485 IC (for U16) |
Where To Buy | Global Sales and Support. Dedicated to advancing safety worldwide. Contact Us